electronic temperature control pcb board SF-105
Features
1 Temperature control/Evap.Fan control
2 Automatic/Manual defrost by electric heater/hot gas
3 High/Low temperature alarm
4 Time/Temp.setting to end defrost
5 °C / °F degrees
6 Mini-sized and integrated intelligent controller
7 Applicable to the compressor of 1HP
Technical Data
1 Range of temperature:-45°C~45°C(-40°F~120°F)
Accuracy:±1°C(± 2°F)
2 Compressor:NO.20A/250VAC
Defrost:NO.10A/250VAC
Evap.Fan:NO.5A/250VAC
Output of the outside sealed transformer:12VAC
3 Temperature sensor:2 NTC
4 Temperature of the operating environment:-10°C~60°C
Relative humidity:20%~90%(Non-condensing)
Size
Dimension:77(L)x35(W)x60(D)mm
Mounting hole dimension:71(L)x29(W)mm
Circuit diagram
Parameter
Parameter | Function | Set range | Default |
E1 | Lower setpoint limit | -45°C/-40°F~Set temp. | -35°C/-31°F |
E2 | Higher setpoint limit | Set temp.~45°C/120°F | 20°C/68°F |
E3 | Temp.hysteresis | 1~10°C/1~18°F | 4°C/7°F |
E4 | Comp.start delay time | 0~10Min | 2Min |
E5 | Offset on room temp. | -5~5°C/°F | 0 |
E6 | Offset on evap.temp. | -5~5°C/°F | 0 |
F0 | Defrost function | 0=Electric heater 1=Hot gas | 0 |
F1 | Max defrost duration | 1~60Min | 20Min |
F2 | Defrost interval time | 0~24Hr | 6Hr |
F3 | Defrost termination temp. | 0~30°C/32~68°F | 8°C/46°F |
F4 | Display during defrost | 0=Normal display 1=Last value before defrost |
0 |
F5 | Fan operating function | 0=Parallel with comp. 1=Continuous running except defrost |
0 |
C1 | Temperature unit | 0=°C 1=°F | 0 |
C2 | High temperature alarm | 0~40°C/°F above setpoint | 20°C |
C3 | Low temperature alarm | -40~0°C/°F below setpoint | -20°C |
C4 | Alarm delay time | 1~90Min | 60Min |